Testing Results
ENERGY STAR was created to help consumers easily identify products, homes, and buildings that save energy and money, and help protect the environment. As the government-backed, trusted symbol for energy efficiency, the ENERGY STAR label identifies highly efficient products and designates superior energy performance in homes and buildings.
- Testing Results
- Wind Charts
| Raised Sill | ||||||
|---|---|---|---|---|---|---|
| Type of Test | Inward Opening Units | Outward Opening Units | ||||
*Air Infiltration: ASTM E-283, ft.³/min/ft. |
@ 1.57 psf (25 mph): 0.15 | @ 1.57 psf (25 mph): 0.12 | ||||
| @ 6.24 psf (50 mph): 0.23 | @ 6.24 psf (50 mph): 0.28 | |||||
*Water Penetration: ASTM E-547 |
No uncontrolled water entry @ 12 psf (68 mph) | No uncontrolled water entry @ 12 psf (68 mph) | ||||
* Structural Load Deflection ASTM E-330: pass |
Top and bottom reinforced locking point unit | Top and bottom reinforced locking point unit | ||||
| Design Pressure Positive @ 45 psf (132 mph) | Design Pressure Positive @ 80 psf (176 mph) | |||||
Design Pressure Negative @ 80 psf (176 mph) |
Design Pressure Negative @ 45 psf (132 mph) |
|||||
| Thermal Perforamnce: Rated, certified and labeled in accordance with NFRC 100 | With 1" (26 mm) thick Insulated Glass: (Top Hung System) | With 1" (26 mm) thick Insulated Glass: (Top Hung System) | ||||
| Type of Glass (1 lite): | U-Factor | +SHGC | ![]() |
U-Factor | +SHGC | ![]() |
| Clear (air filled) | 0.44 | 0.46 | - | 0.45 | 0.46 | - |
| Low E (air filled) | 0.35 | 0.24 | 1 | 0.35 | 0.24 | 1 |
| Low E (argon filled) | 0.33 | 0.37 | 1 | 0.33 | 0.37 | 1 |
| Heat Mirror TC88 (krypton filled) | 0.25 | 0.3 | 1 | 0.25 | 0.3 | 1 |
| * Forced Entry Resistance | In accordance with AAMA-1303.5 and CAWM 300-96 requirements | |||||
| Low Profile Saddle Sill, Standard Flush Sill | ||||||
|---|---|---|---|---|---|---|
| Type of Test | Inward Opening Units | Outward Opening Units | ||||
Water Penetration: ASTM E-547 |
No uncontrolled water entry @ 3.75 psf (38 mph) subject to the following adaptions of the sill in the field by others:
Please note that due to varying site requirements and conditions, these sills will not be prepared for drainge by NanaWall Systems, Inc. If this drainage system is desired, we recommend that a qualified professional construt this system on the project site strictly in accordance with instructions provided by NanaWall Systems, Inc. and in accordance with good waterproofing techniques. note that in some applications drain connetions may not be possible |
|||||
Structural Load Deflection ASTM E-330; pass per engineering leter based on raised sill testing See design windload charts for other sized panels. Note that the structural test pressures were 50% higher than the design pressures. |
Top and bottom reinforced locking point unit | Top and bottom reinforced locking point unit | ||||
| Design Pressure Positive @ 45 psf (132 mph) | Design Pressure Positive @ 80 psf (176 mph) | |||||
| Design Pressure Negative @ 80 psf (176 mph) | Design Pressure Negative @ 45 psf (132 mph) | |||||
| Thermal Performance: Rated, certified and labeled in accordance with NFRC 100 | With 1" (26 mm) thick Insulated Glass: (Top Hung System) | With 1" (26 mm) thick Insulated Glass: (Top Hung System) | ||||
| Type of Glass (1 lite): | U-Factor | +SHGC | ![]() |
U-Factor | +SHGC | ![]() |
| Clear (air filled) | 0.48 | 0.46 | - | 0.48 | 0.47 | - |
| Low E (air filled) | 0.38 | 0.24 | 2 | 0.38 | 0.24 | 2 |
| Low E (argon filled) | 0.36 | 0.37 | 2 | 0.36 | 0.37 | 2 |
| Heat Mirror (krypton filled) | 0.28 | 0.3 | 1 | 0.28 | 0.3 | 1 |
* Forced Entry Resistance |
In accordance with AAMA-1303.5 and CAWM 300-96 requirements. |
|||||
= Energy Star Rating
- meets Energy Star all four climate zones
- meets Energy Star all climate zones, except northern zones
- meets Energy Star Southern and South/Central zones
+ = Solar Heat Gain Coeffiecient
Updated 12/17/2007